- New
Eaton 9SX 8000i RT4U G2
- 8,000 VA / 8,000 W On-Line double-conversion UPS, with pure sine wave output at 230 V single-phase.
- 4U rack or convertible tower format, rack mounting kit included.
- (8) C13 and (4) C19 outlets on hardwired outputs, input via terminal block.
- Automatic internal bypass, LCD display, USB and RS232 ports, one additional card slot.
- Extendable runtime thanks to the connector for external battery modules.
The Eaton 9SX 8000i RT4U G2, part number 9SX8KIRT4UG2, protects critical equipment in a computer room against mains power disturbances. Its On-Line double-conversion technology continuously delivers a regenerated output voltage with a sine wave, to power your servers, storage arrays and network equipment under stable conditions.
Key features
- Double conversion: the output voltage remains stable regardless of the mains condition.
- 97.3% efficiency in normal operation and 99.5% in ECO mode, to limit losses.
- Automatic internal bypass: the load can be switched to mains power if necessary.
- Extendable runtime: a connector allows external battery modules to be attached.
- Monitoring: multilingual graphical LCD display, indicator LEDs, USB (HID compatible) and RS232 ports, and a slot for an expansion card.
- Automatic battery test and deep-discharge protection.
Intended use
This model is designed for computer rooms and server racks. It mounts in a 4U rack using the included mounting kit, or installs as a tower thanks to its convertible format. Input connection is made via terminal block, and outputs are distributed across (8) C13 and (4) C19 outlets.
Technical specifications
| Specification | Value |
|---|---|
| Technology | On-Line double conversion |
| Power | 8,000 VA / 8,000 W |
| Input / output voltage | 230 V single-phase / 230 V single-phase |
| Input voltage range | 176 to 276 V (100 to 276 V with derating) |
| Output waveform | Sine wave |
| Input / output frequency | 40 to 70 Hz / 50/60 Hz |
| Input connector | Terminal block |
| Output outlets | (8) C13, (4) C19 |
| Battery | Sealed VRLA, 12 V, 7 Ah, 20 batteries |
| Typical runtime at half load | 10.6 min |
| Communication | USB + RS232, 1 additional card slot |
| Noise level | < 37 dB at 1 m |
| Format | 4U rack / tower (rails optional) |
| Dimensions (W x D x H) | 440 x 725 x 174 mm |
| Weight | 78.8 kg |
- Type of use
- IT room
- Technology
- ON-LINE Double conversion
- Output Waveform
- SineWave
- Format
- Rack/tower convertible (rails included)
- Power in VA
- 8000
- Power in Watts
- 8000
- Width (mm)
- 440
- Display
- LCD screen
- Height (mm)
- 174
- Depth (mm)
- 725
- Weight (Kg)
- 78,8
- Rack
- 4 U
- Rail kit included
- Yes
- Input voltage
- 230V Single phase
- Output voltage
- 230V single-phase
- Expandable Autonomy
- Socket for adding battery modules
- Redondancy
- No
- Additional card slot
- 1 slot
- Input connector
- Hardwired
- Communication port(s)
- USB + RS232
- Bypass
- Internal automatic By-Pass
- Warranty
- 2 years
Runtime according to the connected load
W
| Load (W) | Internal battery | + 1 battery module(s) | + 2 battery module(s) | + 3 battery module(s) | + 4 battery module(s) | + 5 battery module(s) | + 6 battery module(s) | + 7 battery module(s) | + 8 battery module(s) | + 9 battery module(s) | + 10 battery module(s) | + 11 battery module(s) | + 12 battery module(s) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 400 W | 2 h 46 | 5 h 52 | 9 h 28 | 13 h 36 | 18 h 20 | 10 h 27 | 12 h 42 | 15 h 07 | 17 h 43 | 8 h 50 | 9 h 56 | 11 h 04 | 12 h 14 |
| 800 W | 1 h 21 | 2 h 57 | 4 h 38 | 6 h 26 | 8 h 22 | 10 h 27 | 12 h 42 | 15 h 07 | 17 h 43 | 8 h 50 | 9 h 56 | 11 h 04 | 12 h 14 |
| 1600 W | 36 min | 1 h 25 | 2 h 15 | 3 h 06 | 3 h 59 | 4 h 53 | 5 h 49 | 6 h 47 | 7 h 48 | 8 h 50 | 9 h 56 | 11 h 04 | 12 h 14 |
| 2400 W | 22 min | 53 min | 1 h 28 | 2 h 03 | 2 h 38 | 3 h 15 | 3 h 52 | 4 h 29 | 5 h 08 | 5 h 47 | 6 h 27 | 7 h 08 | 7 h 50 |
| 3150 W | 15 min | 38 min | 1 h 04 | 1 h 30 | 1 h 57 | 2 h 24 | 2 h 52 | 3 h 20 | 3 h 48 | 4 h 17 | 4 h 47 | 5 h 16 | 5 h 46 |
| 4200 W | 10 min | 25,5 min | 44,5 min | 1 h 05 | 1 h 25 | 1 h 45 | 2 h 05 | 2 h 26 | 2 h 46 | 3 h 07 | 3 h 29 | 3 h 50 | 4 h 12 |
| 4780 W | 8 min | 21,2 min | 37,3 min | 54,4 min | 1 h 11 | 1 h 30 | 1 h 47 | 2 h 05 | 2 h 23 | 2 h 41 | 2 h 59 | 3 h 17 | 3 h 36 |
| 5800 W | 6 min | 17 min | 30,5 min | 44,3 min | 58,8 min | 1 h 14 | 1 h 29 | 1 h 44 | 1 h 60 | 2 h 15 | 2 h 31 | 2 h 46 | 3 h 02 |
| 6560 W | 5 min | 13,6 min | 25,2 min | 37,8 min | 50,6 min | 1 h 03 | 1 h 17 | 1 h 30 | 1 h 43 | 1 h 57 | 2 h 11 | 2 h 24 | 2 h 38 |
| 7360 W | 4 min | 11,6 min | 21,4 min | 32,2 min | 43,8 min | 54,6 min | 1 h 06 | 1 h 18 | 1 h 30 | 1 h 42 | 1 h 54 | 2 h 06 | 2 h 19 |
| 8000 W | 3 min | 10 min | 19 min | 29 min | 39 min | 49 min | 1 h | 1 h 10 | 1 h 21 | 1 h 32 | 1 h 43 | 1 h 54 | 2 h 05 |
Typical values provided by Eaton for part number 9SX8KIRT4UG2. Actual runtime depends on battery age and temperature.