Our website is getting a makeover. Some pages may look different for a few days: orders and payments work as usual.
Our website is getting a makeover. Some pages may look different for a few days: orders and payments work as usual.
- New
Eaton 9E 20000i Tour
- 20,000 VA / 16,000 W on-line double-conversion UPS.
- Tower form factor.
- Output: hardwired terminal block.
- Hot-swappable batteries, extendable runtime.
- USB, RS232, network card slot, LCD.
The Eaton 9E 20000i Tour UPS (part number 9E20Ki) is a 20,000 VA / 16,000 W on-line double-conversion UPS in a tower form factor. It continuously supplies a stable, regulated and filtered sine wave, with zero transfer time during a power cut: the most complete protection for servers and sensitive equipment. It accepts a 400 V three-phase or 230 V single-phase input and delivers a 230 V single-phase output.
Key features
- 20,000 VA / 16,000 W, regulated sine wave output.
- Up to 93 % efficiency in double-conversion mode.
- Outputs: hardwired terminal block.
- Hot-swappable batteries, without powering down protected equipment.
- Extendable runtime with the 9EEBM480 battery module.
- USB and RS232 ports, slot for an optional network card, remote shutdown.
- LCD to monitor UPS status and measurements.
What is it for?
For server rooms and industrial sites with a three-phase supply that need a high-power protected single-phase output. Hardwired connection by an electrician.
Technical specifications
| General | |
|---|---|
| Part number | 9E20Ki |
| EAN | 0743172067715 |
| Range | Eaton 9E |
| Power | 20,000 VA / 16,000 W |
| Form factor | Tower |
| Dimensions (W x D x H) | 350 x 706 x 816 mm |
| Weight | 159.8 kg |
| Warranty | 2 years |
| Input | |
| Nominal voltage | 400 V three-phase or 230 V single-phase |
| Voltage range | 176 to 276 V (110 to 276 V with derating) |
| Frequency | 50 / 60 Hz |
| Connection | Hardwired terminal block |
| Output | |
| Topology | On-line double conversion |
| Output voltage | 230 V single-phase (200 / 208 / 220 / 230 / 240 V) |
| Power factor | 0.8 |
| Waveform | Pure sine wave |
| Outputs | hardwired terminal block |
| Efficiency (online) | 93 % |
| Bypass | Automatic internal bypass |
| Battery | |
| Type | Valve-regulated lead-acid (VRLA) |
| Batteries | 40 x 12 V / 9 Ah |
| Replacement | Hot-swappable |
| Runtime extension | Yes, with the 9EEBM480 battery module |
| Communication | |
| Ports | USB (HID compatible), RS232 serial |
| Card slot | 1 slot for an optional communication card (network, relay) |
| Display | LCD |
| Environment | |
| Operating temperature | 0 to 40 °C |
| Noise level | < 55 dB at 1 m |
| Compliance | |
| Standards and certifications | IEC/EN 62040-1, IEC/EN 62040-2, CE, EAC |
Source: Eaton specifications. Runtime depends on load, battery age and temperature.
- Type of use
- IT room
- Technology
- ON-LINE Double conversion
- Output Waveform
- SineWave
- Format
- Tower
- Power in VA
- 20000
- Power in Watts
- 16000
- Width (mm)
- 350
- Display
- LCD screen
- Height (mm)
- 816
- Depth (mm)
- 706
- Weight (Kg)
- 159.8
- Input voltage
- 400V three-phase
- Output voltage
- 230V single-phase
- Expandable Autonomy
- Socket for adding battery modules
- Redondancy
- No
- Additional card slot
- 1 slot
- Input connector
- Hardwired
- Communication port(s)
- USB + RS232
- Bypass
- Internal automatic By-Pass
- Warranty
- 2 years
Runtime according to the connected load
W
| Load (W) | Internal battery | + 1 battery module(s) | + 2 battery module(s) | + 3 battery module(s) | + 4 battery module(s) |
|---|---|---|---|---|---|
| 4000 W | 32 min | 1 h 02 | 2 h 09 | 2 h 26 | 3 h 12 |
| 8000 W | 15 min | 26 min | 58 min | 1 h 02 | 1 h 21 |
| 12000 W | 8 min | 18 min | 36 min | 41 min | 54 min |
| 16000 W | 5 min | 13 min | 26 min | 29 min | 38 min |
Typical values provided by Eaton for part number 9E20KI. Actual runtime depends on battery age and temperature.